Relion® Protection and Control650 seriesIEC 60870-5-103 Communication ProtocolManual

Seite 2

Selection of standard information numbers in controldirection...55

Seite 3 - Product version: 1.1

Section 1 Introduction1.1 This manualThe communication protocol manual describes a communication protocolsupported by the IED. The manual concentrat

Seite 4 - Copyright

1.3 Product documentation1.3.1 Product documentation setPlanning & purchaseEngineeringInstallingCommissioningOperationMaintenanceDecommissioning

Seite 5 - Disclaimer

well as verifying settings by secondary injection. The manual describes the processof testing an IED in a substation which is not in service. The chap

Seite 6 - Conformity

Documents related to REB650 Identity numberProduct Guide, configured 1MRK 505 265-BENType test certificate 1MRK 505 265-TEN Documents related to REL

Seite 7

650 series manuals Identity numberCommunication protocol manual, DNP3 1MRK 511 241-UENCommunication protocol manual, IEC 61850 1MRK 511 242-UENCommuni

Seite 8

• LHMI messages are shown in Courier font, for example:To save the changes in non-volatile memory, select Yes and press .• Parameter names are shown

Seite 9

Table 2: Backup protection functionsIEC 61850 / Functionblock nameANSI Function description Current protectionPHPIOC 50 Instantaneous phase overcu

Seite 10 - Table of contents

Table 3: Control and monitoring functionsIEC 61850 / Functionblock nameANSI Function description ControlSESRSYN 25 Synchrocheck, energizing check

Seite 11 - Section 1 Introduction

IEC 61850 / Functionblock nameANSI Function description I103POSCMD IED commands with position and select for IEC60870-5-103Secondary system supe

Seite 13 - Introduction

IEC 61850 / Functionblock nameANSI Function description VMMXU Phase-phase voltage measurementCMSQI Current sequence component measurementVMSQI

Seite 14 - Section 1 1MRK 511 243-UEN

Table 4: Designed to communicateIEC 61850 / Function blocknameANSI Function description Station communicationIEC61850-8-1 IEC61850 communication

Seite 15 - 1.4 Symbols and conventions

IEC 61850 / Functionblock nameFunction descriptionDTSBEGIN Time synchronizationDTSEND Time synchronizationTIMEZONE Time synchronizationIRIG-B Time syn

Seite 16

Section 2 IEC 60870-5-103 overview2.1 IEC 60870-5-103 standardIEC 60870-5-103 is defined as a companion standard for the informative elementof prote

Seite 17

standard. It should also be noticed that these sets of data are mainly defined for asingle function protection IED. 650 series IEDs in turn are multi

Seite 18

module, the only hardware needed is optical fibres (glass/plastic) and an opto/electrical converter for the PC/RTU.Table 7: Max distances between IED/

Seite 20

Section 3 IEC 60870-5-103 communicationengineering3.1 IEC 60870-5-103 engineering in PCM600The Application Configuration tool (ACT) and the Paramete

Seite 21

The general settings for IEC 60870-5-103 communication are the following:• SlaveAddress and BaudRate: Settings for slave number and communicationspeed

Seite 22

First, set the IED to be synchronized via IEC 60870-5-103 either from IEDConfiguration/Time/Synchronization/TIMESYNCHGEN:1 in PST or from thelocal HMI

Seite 23 - 2.1 IEC 60870-5-103 standard

Document ID: 1MRK 511 243-UENIssued: February 2011Revision: -Product version: 1.1© Copyright 2011 ABB. All rights reserved

Seite 25 - Section 2

Section 4 IEC 60870-5-103 vendor specificimplementationThe signal and setting tables specify the information types supported by the IEDswith the comm

Seite 26

GUID-B8A3A04C-430D-4488-9F72-8529FAB0B17D V1 ENFigure 5: Settings for CMMXU: 1All input signals to IEC 60870-5-103 I103MEAS must be connected in appli

Seite 27 - Section 3

4.1.1.3 SignalsTable 9: I103MEAS Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of service value reportingIL1 REAL 0.0 Service value

Seite 28 - Section 3 1MRK 511 243-UEN

The IED reports all valid measuring types depending on connected signals.Upper limit for measured currents, active/reactive-power is 2.4 times rated v

Seite 29

4.1.2.3 SignalsTable 11: I103MEASUSR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of service value reportingINPUT1 REAL 0.0 Servic

Seite 30

Function type parameter for each block in private range. Default values are definedin private range 25 – 27. One for each instance.Information number

Seite 31 - Section 4

4.1.3.4 SettingsTable 14: I103AR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type

Seite 32 - Section 4 1MRK 511 243-UEN

4.1.4.3 SignalsTable 15: I103EF Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting51_EFFW BOOLEAN 0 Information numb

Seite 33

The delay observed in the protocol is the time difference in between the signal thatis triggering the Disturbance Recorder and the respective configur

Seite 34 - I103MEASUSR

CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imp

Seite 35

Name Type Default Description73_SCL REAL 0 Information number 73, fault location in ohm74_FW BOOLEAN 0 Information number 74, forward/line75_REV BOOLE

Seite 36

Info. no. Message Supported TYPE GI COT64 Start phase L1 Yes 2 Y 1,7,965 Start phase L2 Yes 2 Y 1,7,966 Start phase L3 Yes 2 Y 1,7,967 Start residual

Seite 37

4.1.6.2 Function blockIEC10000292-1-en.vsdI103IEDBLOCK19_LEDRS21_TESTM23_GRP124_GRP225_GRP326_GRP4IEC10000292 V1 ENFigure 11: I103IED function block4

Seite 38 - I103FLTPROT

Info. no. Message Supported23 Setting group 1 active Yes24 Setting group 2 active Yes25 Setting group 3 active Yes26 Setting group 4 active Yes4.1.7

Seite 39

4.1.7.4 SettingsTable 22: I103SUPERV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function t

Seite 40

GUID-391D4145-B7E6-4174-B3F7-753ADDA4D06F V1 ENFigure 13: IEC 60870-5-103I103USRDEF:14.1.8.2 Function blockIEC10000294-1-en.vsdI103USRDEFBLOCK^INPUT1

Seite 41

4.1.8.4 SettingsTable 24: I103USRDEF Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 5 Function t

Seite 42

4.2 Commands in control direction4.2.1 Function commands for IEC 60870-5-103 I103CMD4.2.1.1 FunctionalityI103CMD is a command function block in con

Seite 43

4.2.1.5 Supported information typesFunction commands in control direction, pre-defined I103CMDNumber of instances: 1Function type is selected with pa

Seite 44 - I103USRDEF

4.2.2.4 SettingsTable 30: I103IEDCMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 255 Function

Seite 45

DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a state

Seite 46

4.2.3.3 SignalsTable 31: I103USRCMD Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of commandsTable 32: I103USRCMD Output signalsNam

Seite 47

Function type for each function block instance in private range is selected withparameter FunctionType. Default values are defined in private range 1

Seite 48

4.2.4.4 SettingsTable 36: I103GENCMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 127 - 1 1 Function t

Seite 49 - I103USRCMD

4.2.5.3 SignalsTable 37: I103POSCMD Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of commandPOSITION INTEGER 0 Position of controll

Seite 50

include the function type and the information number for each signal. Formore information on the description of the Disturbance report in the Technica

Seite 51 - I103GENCMD

This section describes all data that is not exactly as specified in the standard.ASDU23In ‘list of recorded disturbances’ (ASDU23) an information elem

Seite 53 - 4.3.1 Disturbance recordings

Section 5 Interoperability5.1 Physical layerTable 39: Electrical Interface SupportedEIA RS-485 Nonumber of loads No5.1.1 Optical interfaceTable 40

Seite 54

5.2.2 Common address of ASDUTable 42: Common address of ASDU SupportedOne COMMON ADDRESS OF ASDU (identicalwith station address)YesMore than one COM

Seite 55

5.2.3.3 Supervision indications in monitor directionTable 45: Supervision indications in monitor directionINF Semantics Supported32 Measurand supervi

Seite 56

ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States rel

Seite 57 - Section 5 Interoperability

INF Semantics Supported84 General start/pick-up Yes85 Breaker failure Yes86 to88Trip measuring system L1 to Trip measuringsystem L3Yes89 Trip measurin

Seite 58 - Interoperability

5.2.4 Selection of standard information numbers in controldirection5.2.4.1 System functions in control directionTable 51: System functions in contro

Seite 59 - Section 5

5.2.5 Basic application functionsTable 54: Basic application functionsSupported Yes Test modeNo Blocking of monitor directionYes Disturbance dataNo

Seite 60

DRA#-Input ACC IEC103 meaning5 5 UL16 6 UL27 7 UL38 8 UN9 64 Private range10 65 Private range11 66 Private range12 67 Private range13 68 Private range

Seite 62 - 5.2.6 Miscellaneous

Section 6 GlossaryAC Alternating currentACT Application configuration tool within PCM600A/D converter Analog-to-digital converterADBS Amplitude deadb

Seite 63

CPU Central processor unitCR Carrier receiveCRC Cyclic redundancy checkCROB Control relay output blockCS Carrier sendCT Current transformerCVT Capacit

Seite 64

FOX 20 Modular 20 channel telecommunication system for speech,data and protection signalsFOX 512/515 Access multiplexerFOX 6Plus Compact time-division

Seite 65 - Section 6 Glossary

I-GIS Intelligent gas-insulated switchgearInstance When several occurrences of the same function are availablein the IED, they are referred to as inst

Seite 66 - Glossary

apparent impedance to the fault applied to the balance point,that is, the set reach. The relay “sees” the fault but perhaps itshould not have seen it.

Seite 67 - Section 6

Table of contentsSection 1 Introduction...5This manual...

Seite 68

SMA connector Subminiature version A, A threaded connector with constantimpedance.SMT Signal matrix tool within PCM600SMS Station monitoring systemSNT

Seite 69

dissemination of standard frequencies and time signals. UTCis derived from International Atomic Time (TAI) by theaddition of a whole number of "l

Seite 72

Contact usABB ABSubstation Automation ProductsSE-721 59 Västerås, SwedenPhone +46 (0) 21 32 50 00Fax +46 (0) 21 14 69 18www.abb.com/substationautomati

Seite 73

Settings......31Supported information types...

Seite 74 - Contact us

Signals.....................42Settings............